Tyco ESFR-34 33.6 K-factor Pendent Sprinklers Early Suppression, Fast Response

Technical Specification

Features:
  • Make: Tyco
  • Model code: ESFR-34
  • ESFR?: Yes
  • Type: Automatic
  • Orientation: Pendant
Additional info:

Early Suppression, Fast Response (ESFR) Suppression-mode sprinklers that are especially advantageous as a means of eliminating the use of in-rack sprinklers when protecting high-piled storage The Tyco Model ESFR-34 Pendent Sprinklers can protect a storage arrangement of 50 ft. (15,2 m) with a ceiling height of 55 ft. (16,8 m) and aisle widths as narrow as 6 ft. (1,8 m) Installed with a maximum element-to-ceiling distance of 17 in. (432 mm) Ceiling-only sprinkler protection of uncartoned (exposed) expanded plastics in accordance with FM Global standards Direct attack on burning fuel by improved heavy sprinkler discharge

Read more
Make Tyco
Manufacturer Tyco Fire Suppression & Building Products
Category Fire Protection>Fire Sprinklers
Model code ESFR-34
ESFR? Yes
Type Automatic
Orientation Pendant
Standards NFPA
Temp. rating (°C) 79~107
Additional info
  • Early Suppression, Fast Response (ESFR)
  • Suppression-mode sprinklers that are especially advantageous as a means of eliminating the use of in-rack sprinklers when protecting high-piled storage
  • The Tyco Model ESFR-34 Pendent Sprinklers can protect a storage arrangement of 50 ft. (15,2 m) with a ceiling height of 55 ft. (16,8 m) and aisle widths as narrow as 6 ft. (1,8 m)
  • Installed with a maximum element-to-ceiling distance of 17 in. (432 mm)
  • Ceiling-only sprinkler protection of uncartoned (exposed) expanded plastics in accordance with FM Global standards
  • Direct attack on burning fuel by improved heavy sprinkler discharge