The Building Engineering Services Association (BESA) has issued an urgent warning about a potential safety weakness in a large number of building ventilation systems due to the incorrect installation of fire dampers.

BESA said it was acting after annual inspections carried out by maintenance contractors found that “a huge number of dampers” had been incorrectly installed.

Head of technical Graeme Fox said that many did not comply with manufacturers’ instructions and needed remedial action “without delay”.

Author's quote

Fox said: “We have been alerted to the very dangerous practice of using self-drilling ‘tek’ screws which do not melt when temperatures rise during a building fireThis means spring-loaded dampers will not be released to contain the spread of fire within the zone and ensure the integrity of the fire-stopping measureDampers must be secured by fusible fixings that allow the duct to break away otherwise the collapsing duct could pull the damper out of place and break the seal between the fire zones.

While this is clearly a very worrying situation, we can take some reassurance from the fact that this problem is being brought to our attention by the increasing frequency of fire damper inspections and tests as awareness grows of this extremely important issue. We would urge contractors to alert their clients immediately so all the necessary checks and repairs can be carried out.”

Download PDF version Download PDF version

In case you missed it

Siemens Expands Fire Safety With Danfoss Acquisition
Siemens Expands Fire Safety With Danfoss Acquisition

Siemens Smart Infrastructure has completed the acquisition of Danfoss Fire Safety, a Denmark-based specialist in fire suppression technology. This strategic step will boost growth...

Specification And Installation: The Key To Effective Door Controls
Specification And Installation: The Key To Effective Door Controls

Safe and seamless movement in our built environment hinges on accurately specified and installed door hardware, explains Russell Marks, managing director of Boss Door Controls. Wi...

AEI Cables: Fire Safety And Building Compliance
AEI Cables: Fire Safety And Building Compliance

Many of the new requirements under the new Building Safety Act 2022 are still not understood by those making critical decisions in the fire safety supply chain, says cable supplier...

vfd