The Wellcome Trust Centre for Human
Genetics is based at the University
of Oxford

The Wellcome Trust Centre for Human Genetics (WTCHG) is a research institute of the University of Oxford, funded by the University, the Wellcome Trust and numerous other sponsors. Its scientific objective is to explore all aspects of the genetic susceptibility of disease, including the understanding of how DNA variants contribute to the risk of disease in the population. Research activities include bioinformatics, cardiovascular disease, genomics, immunity and inflammation, metabolism, neurogenetics, statistical genetics and transgenics.

Since 1999 the WTCHG has been based in the Henry Wellcome Building of Genomic Medicine, which is located on the University of Oxford's Old Road Campus. The WTCHG houses more than 400 occupants spread over three floors.

The original fire alarm and detection system installation, which was more than 10 years old, was in need of replacement. This was driven not only by the age of the system, but by the dwindling availability of spares, very significant costs involved with all maintenance and attendance issues, all of which was brought about by the need for full reliance upon a particular manufacturer because the system was closed protocol.

The University of Oxford Safety Office insists upon open protocol systems, together with commonality of equipment. The reason for this requirement is to be able to have a central maintenance contract with a competent contractor for the whole of the University estate, negating any problems with accessing software or equipment availability. The use of Hochiki devices and Kentec control panels for all replacement and new systems has been the norm for the past twenty years.

Oxfordshire based Pyrotec Services was asked to look at the existing system with a view to total replacement, which included renewing all existing devices and control panels, the retention wherever possible of all existing wiring, the provision of loop powered sounders, the enhancement of detection coverage, and improvement of access for maintenance purposes in certain areas, particularly within ceiling voids and lift shafts.

Following detailed proposals and costs the installation of a new analogue addressable fire alarm and detection system was agreed and funded by the University Safety Office. It was agreed that the new system be based around the Enhanced Systems Protocol (ESP). Stuart Davies, Hochiki’s marketing manager, comments, ‘ESP is a robust total communications solution for intelligent fire detection and fully integrated systems. It has a multi-purpose structure that provides the flexibility and expansion to accommodate simple addressable systems through to integrated building management and safety systems. It is a robust system and perfectly suited for organisations such as WTCHG, where maximum reliability and minimum disruption from unwanted alarms are essential.

''ESP is a robust total communications
solution for intelligent fire detection and

fully integrated systems.'

The project involved installing a 12 loop, 96 zone, analogue control panel and associated devices utilising the existing cabling infrastructure. Approximately 1,000 devices were installed including nearly 500 ACB-E analogue multi-sensors, which incorporate a variable temperature heat element and a rate of rise heat element – both of which are controlled from the control panel, allowing either one or both elements to be active in making the fire decision.

Asked why multi-sensors were the preferred option, Pyrotec’s Paul Slater comments:  “Due to the diversity of work being carried out at WTCHG, it was important to have the option of being able to switch between detection modes on a daily basis. This provides versatility without compromising on safety.

“Access for visual inspection and the maintenance of smoke and heat detectors is essential. The University of Oxford Safety Office specifies that if point detection cannot be installed within a lift shaft in a manner that allows safe access (without the need to stand or ride on the lift car roof) a single zone air-sampling detector is to be installed outside the shaft with a short run of pipe work into the shaft.  Consequently this requirement resulted in the installation of a Hochiki FIRElink aspirating system”. 

As a result of careful planning the installation went very smoothly and was completed with minimal disruption to the activities within the building. Fire detection cover was maintained 24/7 during the installation by carefully interfacing between the new and old systems as the work progressed.

Download PDF version Download PDF version

In case you missed it

The Technologies Of Smart Cities: Their Impact On The Fire Service
The Technologies Of Smart Cities: Their Impact On The Fire Service

To be a smart city, modern urban areas leverage technology to improve operations and services, in effect deploying a network of sensors and devices to collect data on city operatio...

Is Outdated Technology Crippling The Fire Safety And Security Sector?
Is Outdated Technology Crippling The Fire Safety And Security Sector?

In the challenging world of fire safety and security services, organizations are constantly juggling the need to maintain high efficiency with the relentless push for technological...

Rosenbauer Karlsruhe: New Welcome Center In Germany
Rosenbauer Karlsruhe: New Welcome Center In Germany

The new Welcome Center of Rosenbauer Karlsruhe in Germany can already be seen from far away in the city and from the busy highway that runs through Karlsruhe. At night, the strikin...

vfd