Download PDF version

The U.S. Chemical Safety and Hazard Investigation Board (CSB) released its final report into the deadly explosions and fires at the Didion Milling, Inc. (Didion) dry corn milling facility in Cambria, Wisconsin, USA.

The explosion occurred in May 2017, and fatally injured five employees and seriously injured another 14. The incident also ultimately destroyed the facility, resulting in over $15 million in property damage.

source of the smoke

On the night of May 31, 2017, during normal mill facility operations, employees smelled smoke in parts of the mill. They investigated the source of the smoke and determined that it likely was located on the first floor of one of the buildings.

While investigating milling process equipment, several employees heard an explosion and saw fire coming from piping on the rotary gap mill equipment discharge. The employees began to evacuate and attempted to notify other employees of the emergency using their radios, but conflicting radio traffic was confused with the message. 

interconnected dust collection systems

The employees who were not within the immediate vicinity of the observed fire were unaware of the emergency

A fire spread through the process equipment via interconnected dust collection systems resulting in explosions in some of the dust collection equipment. Secondary explosions subsequently occurred throughout the facility.

The employees who were not within the immediate vicinity of the observed fire were unaware of the emergency and the need to evacuate before the explosions.

Combustible dust explosions and fires

CSB Chairperson - Steve Owens said, “Combustible dust explosions and fires can be deadly and incredibly destructive. The tragedy at Didion was made even worse due to the lack of important safeguards in the design of the mill equipment and the lack of engineering controls at the facility that could have reduced the potential for serious fires and explosions." 

He adds, "Our investigation also determined that Didion had a poor safety culture and inadequate leadership on safety issues that contributed to these tragic circumstances.

cause of the dust explosions

The CSB report emphasized that Didion did not recognize the hazards posed by combustible dust

The CSB determined the cause of the dust explosions and collapsed buildings was the ignition of combustible corn dust inside process equipment, which transitioned to multiple explosions.  

The CSB report emphasized that Didion did not recognize the hazards posed by combustible dust throughout the milling process. This resulted in Didion not understanding or addressing those combustible dust hazards.  

Lack of fire risk evaluation

The CSB’s investigation found that a key factor that contributed to the seriousness of the injuries was that Didion did not evaluate the risk of fires nor the need for flame-resistant personal protective equipment. 

Because of this, Didion did not provide personal protective equipment to employees in the mill, some of whom suffered burn injuries during the incident, including some fatal injuries.

no effective corrective measures

The CSB’s investigation further found that the company failed to investigate prior incidents at the mill and implement corrective measures to prevent recurrence.

Despite several previous fires, no effective corrective measures were taken to prevent fires from happening again.

Incident issues

The CSB’s investigation found several issues that contributed to the severity of this incident"

Investigator-In-Charge - Cruz Redman said, “The CSB’s investigation found several issues that contributed to the severity of this incident. They include a lack of hazard recognition, a failure to provide proper engineering controls, and a failure to implement safety management systems to mitigate combustible dust hazards which could ultimately impact the safety of all the workers at the facility.”

insufficient safety regulations

The CSB’s report determined insufficient safety regulations which cover combustible dust operations. While the Occupational Safety and Health Administration (OSHA) regulates some aspects of combustible dust hazards, OSHA does not have an overarching standard to manage the hazards presented by combustible dust. 

As a result, Didion was not required to implement safety management systems, such as those required for other highly hazardous materials.

CSB recommendations

As a result of its findings, the CSB is issuing more than a dozen recommendations to Didion, the National Fire Protection Association (NFPA), and OSHA.

The CSB is recommending that Didion develop a comprehensive combustible dust safety program, which will include management of change, safety information management, fugitive dust management, management of audits, incident investigations, dust hazard analyses, personal protective equipment, and emergency preparedness.

national regulation for industries

CSB is calling on NFPA to update its combustible dust standards to include more requirements

The CSB also is recommending that OSHA develop a national regulation for industries that handle combustible dust, as well as increase follow-up inspections when combustible dust hazards have been identified at facilities.

Similarly, the CSB is calling on the National Fire Protection Association (NFPA), to update its combustible dust standards to include more comprehensive requirements for dust hazard analyses, incident investigations, and management of change.

No citations or fines

The CSB’s board members are appointed by the President subject to Senate confirmation.

The Board does not issue citations or fines but makes safety recommendations to companies, industry organizations, labor groups, and regulatory agencies such as OSHA and EPA.

Download PDF version Download PDF version

In case you missed it

Siemens Expands Fire Safety With Danfoss Acquisition
Siemens Expands Fire Safety With Danfoss Acquisition

Siemens Smart Infrastructure has completed the acquisition of Danfoss Fire Safety, a Denmark-based specialist in fire suppression technology. This strategic step will boost growth...

Specification And Installation: The Key To Effective Door Controls
Specification And Installation: The Key To Effective Door Controls

Safe and seamless movement in our built environment hinges on accurately specified and installed door hardware, explains Russell Marks, managing director of Boss Door Controls. Wi...

AEI Cables: Fire Safety And Building Compliance
AEI Cables: Fire Safety And Building Compliance

Many of the new requirements under the new Building Safety Act 2022 are still not understood by those making critical decisions in the fire safety supply chain, says cable supplier...

vfd