Globe Fire Sprinklers GL8185, dry recessed sidewall
Technical Specification
- Make: Globe Fire Sprinklers
- Model code: GL8185 - recessed horizontal sidewall
- NFPA temperature class: Intermediate
- Standards: NFPA
- Temp. rating (°C): 79~107
Dry recessed horizontal sidewall sprinkler. Listed for light and ordinary harzard with deflector from 4" to 12" below the ceiling. Nominal 'K' factor: 8.1 (116 metric). Thread size: 1" NPT. Length: FM variable to 36". Classification: intermediate. Available sprinkler temperature: 57°C, 68°C, 79°C, 93°C, 141°C. Bulb colour: yellow/green. NFPA maximum ceiling temperature: 66°C. Water working pressure rating: -175 psi. Finishes: factory bronze, satin chrome, bright chrome (available on special order). FM approved.
Read moreMake | Globe Fire Sprinklers |
---|---|
Manufacturer | Globe Fire Sprinkler Corporation |
Category | Fire Protection>Fire Sprinklers |
Model code | GL8185 - recessed horizontal sidewall |
NFPA temperature class | Intermediate |
Standards | NFPA |
Temp. rating (°C) | 79~107 |
Additional info |
Dry recessed horizontal sidewall sprinkler. Listed for light and ordinary harzard with deflector from 4" to 12" below the ceiling. Nominal 'K' factor: 8.1 (116 metric). Thread size: 1" NPT. Length: FM variable to 36". Classification: intermediate. Available sprinkler temperature: 57°C, 68°C, 79°C, 93°C, 141°C. Bulb colour: yellow/green. NFPA maximum ceiling temperature: 66°C. Water working pressure rating: -175 psi. Finishes: factory bronze, satin chrome, bright chrome (available on special order). FM approved. |
Download PDF version Download PDF version |
The New Future For Fire Agencies
DownloadThe Eight Key Trends in Fire Detection in 2023
DownloadA Digital Platform to Improve Fire Safety Compliance and Inspections
DownloadOvercoming the Challenges of Fire Safety in the Paper Industry
DownloadCarbon Monoxide: Creeping Killer Caught In The Act
Download