Two loop analogue addressable fire alarm panel, designed to be as simple to use as a conventional fire alarm panel. Two addressable loops (divided into 16 zones) and 4 conventional sounder circuits. Supports a serial repeater, includes a real time clock and has 2,048 capacity event log. Loop capacity: 126 devices. Flame retardant ABS plastic. Set of changeover relay contacts for fault condition. One man test mode. Plug & play, no need for any special tools or laptop. Fully integrated qwerty keypad. All associated devices are loop powered. System voltage: 24 V DC.
Make | Zeta |
---|---|
Manufacturer | GLT Exports Ltd |
Model code | NPAD |
Additional info |
Two loop analogue addressable fire alarm panel, designed to be as simple to use as a conventional fire alarm panel. Two addressable loops (divided into 16 zones) and 4 conventional sounder circuits. Supports a serial repeater, includes a real time clock and has 2,048 capacity event log. Loop capacity: 126 devices. Flame retardant ABS plastic. Set of changeover relay contacts for fault condition. One man test mode. Plug & play, no need for any special tools or laptop. Fully integrated qwerty keypad. All associated devices are loop powered. System voltage: 24 V DC. |