Microprocessor based conventional fire alarm control panel. Two detection zones. One set of volt free changeover contacts operable on fire. Head removal via zener clamp or active end-of-line unit. Open collector fault output. Zone and alarm disablement. Maximum number of detectors per zone: 30. Number of alarm zones: 2. Maximum number of sounders per zone: 10. System voltage: 28.4 V DC. Panel dimensions: 234 x 225 x 85 mm. Complies to EN54-2 & 4.
Make | VRC Terofire |
---|---|
Manufacturer | Terofire Products (Telelarm VRC) |
Model code | Saffire 2 |
Additional info |
Microprocessor based conventional fire alarm control panel. Two detection zones. One set of volt free changeover contacts operable on fire. Head removal via zener clamp or active end-of-line unit. Open collector fault output. Zone and alarm disablement. Maximum number of detectors per zone: 30. Number of alarm zones: 2. Maximum number of sounders per zone: 10. System voltage: 28.4 V DC. Panel dimensions: 234 x 225 x 85 mm. Complies to EN54-2 & 4.
|