1 Extinguishing area for max. 1.600 m² acc. to VdS 8 detector zones for up to 30 Series 9200 and IQ8Quad automatic detectors each (for two-detector dependency up to 25 detectors) 1 zone for manual alarm 1 zone for emergency stop 8 relays, monitored or floating 30V DC/2A 3 relays, floating 30V DC/2A 2 mains voltage relays, floating 230V AC/2A All outputs are provided with fuses
Make | Esser by Honeywell |
---|---|
Manufacturer | Esser by Honeywell |
Model code | 8010 series 4 w/o operating unit |
Additional info |
|